跳到正文
arXiv (Robotics + Hardware + Signal)· Cletus Ngwerume, Lang Tong, Chee-Wooi Ten, Yi Hu·· 1 天前AI 评分24

面向AI数据中心制冷负荷仿真的闭环热动态模型

A Closed-Loop Thermal Dynamic Model for AI Data Center Cooling Load Simulation

AI 导读

该研究提出一种闭环仿真框架,将线性热动态模型与基于死区的控制相结合,以捕捉非线性制冷行为。框架基于Marconi100超级计算机的运行数据验证,平均绝对误差从95.80 kW降至23.52 kW,均方根误差从109.79 kW降至29.91 kW,并改善了对日峰值需求和日内波动的复现。

正文 · 原文

arXiv:2607.28962v3 Announce Type: replace-cross Abstract: Accurate modeling and simulation of cooling electricity demand is essential for characterizing AI data center loads, but time-synchronized operational measurements are scarce. Constant coefficient-of-performance models can oversimplify cooling behavior, while detailed thermal state-space models are cumbersome to use. This paper proposes a closed-loop simulation framework that couples a linear thermal dynamic model with deadband-based control to capture nonlinear cooling behaviors. The framework is validated against operational data from the Marconi100 supercomputer. Compared with the baseline, the proposed model reduces the mean absolute error from 95.80 to 23.52 kW and the root-mean-square error from 109.79 to 29.91 kW. The statistical evaluation further shows improved reproduction of daily peak demand and intraday variability. The framework provides a computationally tractable approach to generate physically interpretable cooling load profiles for power system studies.

来源:arXiv (Robotics + Hardware + Signal) · arxiv.org